Wet-bulb temperature at 30 °C and 50 % humidity

The wet bulb shows the limit of adiabatic cooling: at 30 °C and 50 % it is about 22 °C and the enthalpy of the air is about 64 kJ/kg.

Parameters

Result

Approximate calculation using a simplified model: for designing equipment and process modes, consult a technologist.

Calculation example

What we calculate
Air state
Air temperature
30 °C
Relative humidity
50 %
Humidity ratio
13,28 g/kg of dry air
Dew point
18,4 °C
Wet-bulb temperature
22,0 °C
Enthalpy
64,1 kJ/kg
Density of humid air
1,155 kg/m³
Saturation vapour pressure
4,24 kPa

Frequently asked questions

Why know the wet-bulb temperature?
It is the minimum temperature to which water can be cooled by evaporation (cooling tower) and the limit of the drying rate.

The calculations are approximate: they help to assess the process and compare options, but do not replace a process design and trials on a specific raw material. This section is for reference only and contains no commercial offers.